Home Products News Contact 0866.898.966
Home / News / Operating Rooms & Negative-Pressure Isolation Rooms in Hospitals: The 3-Stage Filter System
26 May 2026

Operating Rooms & Negative-Pressure Isolation Rooms in Hospitals: The 3-Stage Filter System

Operating Rooms & Negative-Pressure Isolation Rooms in Hospitals: The 3-Stage Filter System

After the COVID-19 pandemic, Vietnamese hospitals invested more heavily in negative-pressure isolation rooms. Alongside these, ISO 5/7 operating rooms, ICUs, and microbiology lab rooms all need specialised air filtration. This article rounds up the technical requirements for the four most important room types in a modern hospital.

1. The Standard Operating Theatre

General requirements

An operating theatre is a high-sterility area — any bacterium that lands in a wound can cause an SSI (Surgical Site Infection), prolonging treatment and raising mortality.

Common international standards: DIN 1946-4 (Germany), ASHRAE 170 (US), HTM 03-01 (UK). Vietnam references these for international-grade hospitals.

OR classification

OR class Surgery type Cleanroom class Filter train
Class I (Ultra-clean) Organ transplant, joint-replacement orthopaedics ISO 5 under LAF Pre G4 + F9 + HEPA H14 + ceiling LAF
Class II (High) Cardiac, bone-marrow transplant, paediatric surgery ISO 7 Pre G4 + F8 + HEPA H13
Class III (Standard) GI, obstetric, general surgery ISO 7 in operation Pre G4 + F8 + HEPA H13
Class IV (Septic) Infected surgery (amputation, peritonitis) Negative pressure, ISO 7 Pre G4 + F8 + HEPA H13 on both supply and exhaust

Air velocity and flow

  • ACH: 20-25 per hour for standard ORs, 40+ per hour for joint-replacement orthopaedic ORs.
  • LAF velocity: 0.25-0.35 m/s at the operating plane (lower than pharma cleanrooms to avoid drying the wound).
  • LAF coverage: covers the operating table, minimum 3×3 m.

Temperature and humidity

  • Temperature: 19-24°C (flexible per surgeon's preference).
  • Humidity: 30-60% RH.
  • Differential pressure: +15 Pa relative to the surgical corridor.

2. Negative-Pressure Isolation Room

When are they needed?

  • Isolating patients with suspected or confirmed airborne infections: TB, measles, chickenpox, COVID, MERS, SARS, Ebola, monkeypox.
  • Hazardous-sample collection rooms.
  • Autopsy rooms for infectious cases.

Design principles

Pressure inside the room is lower than the corridor (-15 Pa or below). When the door opens, air flows "into" the room rather than out — keeping pathogens contained.

Standard structure

  • Anteroom between corridor and isolation room — at -5 Pa vs. corridor, +10 Pa vs. main room.
  • Airtight doors with gaskets on both ends.
  • Glass observation window to monitor from outside.
  • Pass boxes for food, medicines, and samples.

Filter train

Supply air:

Pre G4 → Medium F8 → HEPA H13 (ceiling terminal box).

Exhaust air:

HEPA H14 at the exhaust inlet (in-line HEPA) → dedicated exhaust fan → discharge stack rising 3 m above the roof.

The exhaust HEPA is more important than the supply HEPA — it is the last barrier preventing pathogens from escaping. Every 6 months, integrity test and seal the housing when replacing it (to prevent technician exposure).

Safe HEPA replacement procedure

  1. Decontaminate the room before shutting down the system.
  2. Bag-in/Bag-out housing: the HEPA housing has an integrated PE bag enclosing the filter.
  3. Dispose per hazardous-waste protocol.
  4. Integrity-test the new HEPA before returning to service.

3. ICU (Intensive Care Unit)

Requirements

  • ICU patients are immunocompromised — the environment must be cleaner than a regular ward.
  • Filter train: Pre G4 + Medium F8 + HEPA H13.
  • ACH: 12-15 per hour.
  • Temperature: 22-24°C; humidity: 40-60%.
  • Pressure: +5 Pa relative to the corridor.

Negative-pressure ICU

For ICU patients who need both critical care and respiratory isolation. The configuration combines ICU + negative-pressure room — capex runs 1.5-2× a standard ICU.

4. Hospital microbiology lab (BSL-2 / BSL-3)

BSL-2 (Biosafety Level 2)

  • Routine bacteriology, blood culture, GI microbiology.
  • Filter train: Pre G4 + Medium F8 in the AHU; BSC class II biosafety cabinet with internal HEPA H14.

BSL-3

  • TB, respiratory viruses, SARS, COVID, category-B bacterial pathogens.
  • Negative-pressure room at -25 Pa.
  • Pre G4 + Medium F8 + HEPA H13 on supply; HEPA H14 bag-in/bag-out on exhaust.
  • Exhaust fan with backup (UPS + generator) — must not stop while occupants are inside.
  • Class II BSC with dual HEPA (supply + exhaust) ensures no air escapes the cabinet.

BSL-4

  • Vietnam currently has no civilian BSL-4. This level is for Ebola, Marburg, Lassa.
  • Requires a "suit" lab — technicians wear positive-pressure suits; lab exhaust passes through double HEPA + thermal destruction.

5. HVAC system for a general hospital

Overall structure

  • Dedicated AHU per zone:
  • OR AHU (5-8 rooms per AHU).
  • ICU AHU.
  • Negative-pressure isolation AHU.
  • Surgical corridor AHU.
  • Outpatient AHU.
  • 70-80% recirculation for outpatient and corridor areas.
  • 100% fresh-air for ORs and negative-pressure rooms.

Sensors and BMS

  • Differential-pressure sensors in every room — alarm on ±5 Pa deviation from setpoint.
  • Temperature, humidity, and online particle counters in ORs and ICUs.
  • BMS integrated with the EMR system — logs everything for post-incident traceability of SSIs.

6. Validation and maintenance for OR / isolation rooms

Recommended frequency

  • Daily: check differential pressure, temperature, humidity.
  • Weekly: clean ceilings, floors, walls with disinfectant.
  • Monthly: check ΔP across each filter; clean Pre Filters.
  • Quarterly: clean and inspect Medium Filters.
  • Every 6 months: DOP/PAO test HEPAs (Class I ORs and isolation rooms).
  • Annually: comprehensive re-qualification, particle count per ISO 14644.
  • Every 3-5 years: replace HEPAs.

Smoke airflow visualisation test

  • LAF ORs: every 6 months — verify laminar flow is even with no reverse eddies.
  • Isolation rooms: annually — verify air flows "into" the room from the anteroom.

7. Real-world case: COVID-era negative-pressure isolation rooms

During 2020-2022, dozens of Vietnamese hospitals converted regular wards into emergency negative-pressure isolation rooms. Lessons learned:

  • You cannot "rig" negative pressure with a lone exhaust fan — you need the full supply - exhaust - bag-in/bag-out HEPA chain.
  • Exhaust HEPA H14 is mandatory — without it, pathogens dispersed into the hospital's surrounding air.
  • Anterooms cut staff infection risk by 5-10×.
  • UPS-backed exhaust fans — a power outage in an isolation room is a life-threatening event.

8. Standard OR + isolation investment for new hospitals

Indicative costs (equipment included):

  • Class II standard OR: 2-4 billion VND per room.
  • Class I ultra-clean OR: 4-8 billion VND per room.
  • Negative-pressure isolation room: 1.5-3 billion VND per room.
  • Standard ICU: 1-2 billion VND per bed (ventilator, monitor, HVAC included).

Conclusion

Operating theatres, negative-pressure isolation rooms, and ICUs are the three backbone components of a modern hospital. Investing properly in the HVAC - HEPA - ULPA system reduces SSI rates, protects healthcare workers, and prepares the hospital for future outbreaks.


About Green Filter

Green Filter supplies HEPA H13/H14, ULPA, bag-in/bag-out housings, Medium F8/F9, and Pre Filters for operating rooms, negative-pressure isolation rooms, ICUs, and BSL-2/BSL-3 labs. Products come with full EN 1822-1:2009 certificates and PAO scan tests.

📞 Contact Green Filter for filter consulting for your hospital project: [insert hotline / email / website]

See also: What is a cleanroom? · HEPA/ULPA validation and replacement · BSL-2/BSL-3 microbiology and research labs.

Back to News